12 AWG voltage drop at 100 feet

You already have 12 AWG in mind. This page only answers whether 100 ft still fits your percent.

Calculate voltage drop

How to run this check

  1. Open Voltage Drop and lock the size at 12 AWG.
  2. Enter the real voltage, load current, and one-way feet.
  3. If it is over target, read the suggested larger size or switch to Wire Size.

Why 120 V looks worse than 240 V

The volt drop is the same for the same current, size, and feet. The percent is volts dropped divided by system voltage, so 120 V doubles the percent compared with 240 V.

That is why a 100 ft 12 AWG run can be a problem on a 120 V branch and still look acceptable on 240 V (3.3% in this example).

Do not use a rule of thumb in place of the percent

“100 ft needs one size up” is a memory aid, not a check. Motor loads, 3-phase, and a lighter actual current all change the number.

If you already know the AWG, stay on the voltage-drop tool. Use Wire Size only when you want the next size that clears both checks.

12 AWG copper, 20 A, 100 ft one-way, single-phase

VoltageDropPercent3% target
120 V7.9 V6.6%Over target
240 V7.9 V3.3%Over target

Related

FAQ

Is 100 ft of 12 AWG always too long?

No. It depends on voltage and current. 20 A at 120 V is over 3% in this example. The same feet at 240 V is close to the line.

Do I enter one-way feet or round trip?

Enter one-way feet. The single-phase math already uses the 2-wire path.

Planning reference only. Verify against the current NEC, manufacturer data, and the authority having jurisdiction. This is not engineering advice or a license substitute.