Voltage Drop Calculator
Estimate voltage drop for electrical wire runs by conductor material, length, current, and voltage so you can choose safer circuit designs.
Check whether a wire run stays within an acceptable voltage drop range before you commit to a conductor size.
- Built for branch-circuit and feeder planning where long runs can cause nuisance trips, dim lights, or poor motor starting.
- Keeps voltage, current, conductor material, and distance visible together so the tradeoff is easy to understand.
- Best used before final ampacity/code checks, not as a replacement for NEC/IEC requirements.
Calculate voltage drop in electrical cables
💡 Calculates voltage drop considering temperature and material
Formula: VD = (2 × ρ × I × L) / A
ρ adjusted for temperature: ρ(T) = ρ(20°C) × [1 + α × (T - 20)]
Acceptable: ≤ 5% voltage drop
- System voltage
- Load current in amps
- One-way wire run length
- Copper or aluminum conductor
- Acceptable voltage-drop percentage
Example: 20 A load on a 120 V branch circuit
- • 120 V single-phase circuit
- • 20 A load current
- • 75 ft one-way copper run
- 1. Enter 120 V, 20 A, 75 ft, and copper as the conductor material.
- 2. Compare the calculated voltage drop percentage against a 3% planning target.
- Long lighting or receptacle circuits
- Detached garage or outdoor feeder planning
- Motor or pump circuits with starting sensitivity
- Around 3% or less is commonly used as a branch-circuit design target.
- A higher percentage means the load receives less voltage and may run hotter or less efficiently.
- If the result is high, compare a larger conductor, shorter run, or lower current design.
- Voltage drop recommendations are separate from mandatory ampacity rules.
- Temperature, conduit fill, bundling, insulation type, and local code can change the final conductor choice.
- Use manufacturer data and authority-having-jurisdiction guidance for real installations.
Frequently asked questions
What is voltage drop?
Voltage drop is the loss of voltage along a conductor caused by resistance in the wire.
Why does voltage drop matter?
Excessive voltage drop can reduce equipment performance, cause heating, and indicate poor conductor sizing.
Does material matter?
Yes. Copper and aluminum have different resistance values, so the same current and length can produce different drops.
Is this NEC compliant?
Use the output as a planning aid and verify final installations with NEC or your local electrical code.